Why a 19.8 m earth tube in Riyadh only cools the air by 4.8 K

A 2026 Energies paper buries one clay pipe under a Solar Decathlon house. Its effectiveness, its 4.8 K drop and its 534 kWh a year all fall out of one effectiveness-NTU calculation.

Bury a pipe deep enough and the ground around it stays near the yearly average temperature all summer. Draw outdoor air through it and the air comes out cooler, for the price of a fan. A 2026 paper in Energies does exactly that under a Solar Decathlon house in Riyadh — one vitrified clay pipe, 19.8 m long, 0.30 m across, buried 6 m down — and reports an honest, modest result: a mean 4.8 K of cooling, 534 kWh of sensible cooling a year, and 2.4 % off the house’s air-conditioning bill. A buried pipe is a heat exchanger with soil on one side, so almost all of that can be rebuilt with the heat exchanger sizing tool. The air-side flow regime comes from dimensionless numbers calculator, and the house load from HVAC load.

The paper in brief

The house is small: 81 m² of conditioned floor, about 243 m³. Its ventilation requirement under ASHRAE 62.2 is 20 L/s of outdoor air, which the authors route through the buried pipe before it reaches the air handler. The soil at 6 m sits between 23.3 and 27.5 °C through the year, averaging 25.4 °C, against a Riyadh cooling design dry bulb of 42.3 °C.

Their reported performance:

  • Pipe effectiveness 0.54 at NTU 0.78 at their tool’s design point of 43.5 L/s per pipe, and 0.65 at the actual 20 L/s, with a simulated median of 0.59.
  • Mean air temperature drop 4.8 K over 4623 cooling hours, maximum 12.6 K; mean rise 7.8 K over 360 heating hours.
  • 534 kWh/yr of sensible cooling delivered, 247 kWh/yr of air-conditioning electricity saved, 68 kWh/yr of electric heating displaced, 45 kWh/yr of fan energy, leaving 270 kWh/yr net — 2.4 % of the house’s HVAC electricity.
  • Push the ventilation up to 6.4 air changes per hour and the saving reaches 32 %, but that is no longer a ventilation system.

The paper’s own conclusion is that ground-coupled ventilation does not close the gap to zero carbon on its own. The numbers below say why, and they are all checkable.

Checked with the tools

A buried pipe is the easiest kind of heat exchanger to analyse: the soil is so much larger than the airstream that its capacity rate is effectively infinite, so the capacity ratio Cr is zero and the effectiveness is simply ε = 1 − e^(−NTU), whatever the arrangement. That is the branch heat exchanger sizing takes when one stream dwarfs the other.

Step 1: the paper’s own pair is consistent. Feeding NTU = 0.78 with Cr = 0 into the tool’s effectiveness gives ε = 0.5416, against the paper’s 0.54. Going the other way, ε = 0.54 needs NTU = 0.7765. The paper’s 0.65 at 20 L/s needs NTU = 1.0498. So the two published effectiveness values are not independent claims: they say the pipe’s NTU rises by 35 % when the flow is cut by more than half.

Step 2: back out the overall heat transfer coefficient, and see where it comes from. The pipe’s surface area is π × 0.30 × 19.8 = 18.66 m². At 43.5 L/s the air’s capacity rate is 52.6 W/K, so NTU = 0.78 means UA = 41.1 W/K and U = 2.200 W/m²K. At 20 L/s the capacity rate is 24.2 W/K and NTU = 1.0498 means U = 1.361 W/m²K.

Is that physical? dimensionless numbers calculator‘s maths puts the air at 0.615 m/s and Re = 12,300 at the design point, and 0.283 m/s and Re = 5650 at 20 L/s — turbulent both times, but only just at the lower flow. Applying the Dittus-Boelter correlation (a textbook formula, not a fibub tool) gives an air-side film of 3.318 W/m²K at the design point. Subtracting it from the overall 2.200 leaves 0.153 m²K/W for the clay wall and the soil around it, which does not change with the airflow.

Now predict the low-flow case from that split. The film falls to 1.782 W/m²K, the fixed 0.153 stays, and the overall U becomes 1.400 W/m²K — against the 1.361 the paper’s own 0.65 implies. Turned back into effectiveness, our model gives 0.660 where the paper gives 0.65. The two chains agree to 1.5 %.

That also explains the shape of the thing. If the air film were the only resistance, U would scale as the flow to the power 0.8. The paper’s two points imply a power of 0.618, because the soil is in series and does not care how fast the air goes.

Earth-tube effectiveness against airflowEarth-tube effectiveness against airflow0.20.40.60.8120406080100Airflow through one pipe (L/s)Effectiveness εSeries-resistance modelThe paper's two pointsfibub.com
Figure 1. Effectiveness of the paper's buried pipe against airflow. The line is our series-resistance model: a Dittus-Boelter air film plus a fixed resistance for the clay wall and the soil, pinned to the paper's design point and then turned into effectiveness by the Heat exchanger sizing tool's maths. The two dots are the paper's own published values.

Step 3: the energy adds up exactly. At 20 L/s the air carries 24.20 W/K. Multiply by the mean 4.8 K and you get 116 W of cooling; over 4623 hours that is 537 kWh, against the paper’s 534 kWh/yr — 0.6 % apart, which is our rounded air density. The heating side: 24.20 W/K × 7.8 K × 360 h = 68.0 kWh, exactly the paper’s 68. So the paper’s annual energies are internally consistent with a single capacity rate, and anyone can re-derive them in one line.

Running it the other way is more interesting. If the effectiveness really is 0.65, a mean drop of 4.8 K means the mean outdoor air during cooling hours was 32.8 °C, and the maximum drop of 12.6 K means a peak of 44.8 °C — both believable for Riyadh, and a check that the reported drops belong to the reported effectiveness.

Check Paper Tool gives
Effectiveness at NTU 0.78, Cr = 0 0.54 0.5416
NTU behind ε = 0.65 — 1.0498
Overall U at 20 L/s — 1.361 W/m²K (from ε), 1.400 (from the film split)
Effectiveness at 20 L/s 0.65 0.660 (predicted from the design point)
Sensible cooling a year 534 kWh 537 kWh
Electric heating displaced 68 kWh 68.0 kWh

Step 4: why 19.8 m is not enough, and why 40 m would not fix it. Figure 2 stretches the buried run at 20 L/s. Effectiveness climbs steeply to about 20 m and then flattens, because each extra metre works on a smaller remaining temperature difference. Reaching ε = 0.80 needs 29.5 m and ε = 0.90 needs 42.2 m — more than twice the pipe for a quarter more of the available drop, and every one of those metres has to be dug 6 m deep.

Effectiveness against pipe length at 20 L/sEffectiveness against pipe length at 20 L/s0.20.40.60.8120406080100120Horizontal pipe run (m)Effectiveness εε = 0.90the paper's 19.8 mfibub.com
Figure 2. The same model at 20 L/s, with the buried run stretched from 5 to 120 m. The dot is the paper's 19.8 m pipe.

Rated as the tool rates an exchanger — U·A = 26.1 W/K against 42.3 °C inlet air and 25.4 °C soil — the pipe delivers 270 W and drops the air by 11.2 K, to 31.1 °C. On the worst afternoon of the year, a buried pipe hands the air handler air that is still 6 K above the room setpoint. It is a pre-cooler, not a cooling system, which is the paper’s point made with its own numbers.

How we made the graphs

Both charts and every number above come from scripts/blog-figures/earth-air-tube-riyadh-effectiveness-ntu-temperature-drop.mjs in fibub’s public code. It calls effectiveness, ntuFor and rate from src/lib/sci/eng-hx.ts, the maths behind heat exchanger sizing, and dimensionless from src/lib/sci/phdimless.ts, the maths behind dimensionless numbers calculator, for the velocity, Reynolds and Prandtl numbers.

From the paper: the pipe’s length, bore and depth, the two airflows, the published NTU and both effectiveness values, the soil temperature, the cooling and heating drops and hours, and the annual energies. Our assumptions: air taken at the tool’s rounded 20 °C properties (1.204 kg/m³, 1005 J/kgK, 0.0257 W/mK) over the whole flow range rather than at each local temperature; the Dittus-Boelter exponent 0.3 for a cooled gas; only the horizontal 19.8 m counted as heat transfer surface, not the two risers; and the series-resistance split in Step 2, which is a model fitted to the paper’s design point, not a value the paper publishes.

How we test the maths

tests/sci-tools/heat-exchanger-sizing.mjs runs inside tests/sci.mjs on every change to fibub:

  • The effectiveness-NTU relations for counterflow, parallel flow, shell-and-tube and all three crossflow cases are pinned against an independent Python implementation, including the exact unmixed-crossflow series.
  • ntuFor must invert effectiveness to within 1 part in 10⁹ for every arrangement, and the log-mean temperature difference and the 1-2 shell correction factor F are checked against published worked examples.
  • New with this article: effectiveness('counter', 0.78, 0) must give 0.5415939886947765 and ntuFor('counter', 0.65, 0) must give 1.0498221244986778, the Cr = 0 limit this article rests on; and the rating of a 26.12 W/K earth tube against 42.3 °C air and 25.4 °C soil must give an outlet of 31.14211923595775 °C, an effectiveness of 0.6602296310084169 and a duty of 270.02517764212797 W.

Check it yourself

On the heat exchanger sizing tool page, to reproduce Step 4’s rating:

  1. In Streams, set Hot inlet (°C) to 42.3, Hot flow (kg/s) to 0.02408 (20 L/s of air at 1.204 kg/m³) and Hot cp (kJ/kg·K) to 1.005.
  2. Set Cold inlet (°C) to 25.4, Cold flow (kg/s) to 10000 and Cold cp (kJ/kg·K) to 1. That huge flow is how you tell the tool “the other side is the ground”: it makes the capacity ratio essentially zero.
  3. In Exchanger, choose Counterflow (double pipe) — with one side infinite, every arrangement gives the same answer.
  4. Set Overall U (W/m²·K) to 1.4 and Find to Outlets for an area (rating), then Area (m²) to 18.66.
  5. The Results card reads NTU about 1.08, effectiveness 0.66, a duty near 270 W and a hot outlet of about 31.1 °C — an 11.2 K drop, Step 4’s number.
  6. Now change Area (m²) to 39.8 (a 42.2 m run) and watch the effectiveness climb only to about 0.90 while the duty rises from 270 to 368 W. Changing Hot flow (kg/s) to 0.05236 (43.5 L/s) and Overall U to 2.2 returns the paper’s design point: NTU 0.78, effectiveness 0.54.

What researchers can use it for

  • Check a published effectiveness against its NTU in one step, before building anything on it: with one stream much larger than the other, ε = 1 − e^(−NTU) and nothing else.
  • Back out an overall U from a reported effectiveness and known geometry, then ask whether a film correlation can supply it, as in Step 2.
  • Separate a flow-dependent film from a fixed resistance, which tells you whether a system will respond to a bigger fan or only to more surface.
  • Size a buried pipe, a coil or a recovery wheel for a target effectiveness and see the diminishing returns before quoting a length.
  • Carry the pre-cooled air into the room with HVAC load, where its sensible and latent effect on the coil can be read off.

The fine print

  • The series-resistance split in Step 2 is our model, pinned to the paper’s own design point. It reproduces the paper’s second effectiveness to 1.5 %, which is support, not proof.
  • We counted only the 19.8 m horizontal run as heat transfer surface. The two 6.3 m risers pass through shallower, warmer soil and would add some area and some loss, so our U is an upper figure.
  • Air properties were taken as constant at the tool’s rounded 20 °C values. At 42 °C the density is about 11 % lower, which moves the capacity rate and the annual energy by about the same amount.
  • Soil temperature at depth is itself a yearly wave, not a constant. The paper’s 23.3 to 27.5 °C range matters: run the Step 4 rating at 27.5 °C and the peak drop falls from 11.2 to about 9.8 K.
  • A buried pipe does nothing about moisture, and in humid climates it can condense inside the tube. Riyadh is dry; do not copy the design to a coastal site without checking the dew point.

Sources

  • Alanazi, O., Kotbi, M. G., Alfadil, M. O. and Kotbi, A. G. (2026), Can Ground-Coupled Ventilation Close the Gap to Zero Carbon? Hourly Simulation and Techno-Economic Assessment of a Solar Decathlon House in Riyadh, Energies 19(21): 5355, doi:10.3390/en19215355. Licence CC BY, checked on the MDPI article page, 2026-11-24. Values used here: horizontal buried run 19.8 m with two 6.3 m risers, bore 0.30 m, burial depth 6.0 m, vitrified clay pipe of wall conductivity 1.6 W/mK; outdoor air 20 L/s (ASHRAE 62.2) and a tool design point of 43.5 L/s per pipe; mean air velocity 0.28 m/s and 0.62 m/s; analytical pipe effectiveness 0.54 at NTU 0.78 (design point) and 0.65 at 20 L/s, with a simulated median of 0.59; undisturbed soil at 6 m between 23.3 and 27.5 degrees C, mean 25.4; limestone conductivity 2.0 W/mK and soil thermal diffusivity 1.5e-6 m2/s; mean cooling temperature drop 4.8 K over 4623 h, maximum 12.6 K, mean heating rise 7.8 K over 360 h; sensible cooling delivered 534 kWh/yr, HVAC electricity saved 247 kWh/yr, heating displaced 68 kWh/yr, fan energy 45 kWh/yr, net 270 kWh/yr; conditioned floor area 81 m2 and volume about 243 m3; Riyadh mean air temperature 25.7 degrees C, cooling design dry bulb 42.3, heating design 5.0; fan 9 W against 135 Pa; 2.8 % gross and 2.4 % net HVAC saving, rising to 32 % at 6.4 air changes per hour.